Verify the module chassis size – Rockwell Automation 1734-AENT, Series B POINT I/O EtherNet/IP Adapter Module User Manual User Manual
Page 55

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013
45
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
4. Choose Download.
The Download dialog opens with a reminder of the following.
•
The controller is in Remote Run mode.
•
The mode changes to Remote Program prior to download.
5. From the Download dialog, choose Download
The RSLogix 5000 software dialog opens.
6. Notice that the 1756-ENBT Bridge is now online.
If yellow triangles are present, see the following section.
Verify the Module Chassis
Size
You have now built the I/O tree in the RSLogix 5000 software, and the
RSLogix 5000 software used the chassis size from the 1734-AENT General tab.
Now you need to download this new chassis size value into the 1734-AENT
adapter hardware. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the 1734-AENT adapter hardware.
1. Verify that the RSLogix 5000 software is online.
2. In the Project dialog, right-click the 1734-AENT adapter under I/O
Configuration.