Configure the adapter with fixed ip address – Rockwell Automation 1734-AENT, Series B POINT I/O EtherNet/IP Adapter Module User Manual User Manual
Page 58

48
Rockwell Automation Publication 1734-UM018B-EN-P - October 2013
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Configure the Adapter with
Fixed IP Address
To configure the adapter with a fixed IP address to prevent the adapter from
ceasing to communicate with the ControlLogix controller:
1. All controllers with I/O connections to the AENT and/or the modules in
its backplane need to be in program mode.
2. In the Module Properties dialog, click the Internet Protocol tab.
3. If it is not selected, select Manually configure IP settings.
4. Enter values for Physical Module IP Address, and Subnet Mask, noting we
used the following values:
5. Click Set
6. Read and acknowledge the warning.
7. Click Yes.
8. Click the Refresh communication button to verify the changes.
Physical Module IP Address
192.168.1.29
Subnet Mask
255.255.255.0