Rockwell Automation 1734-AENT, Series B POINT I/O EtherNet/IP Adapter Module User Manual User Manual
Page 83

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013
71
Troubleshoot the Adapter Chapter 6
POINTBus Status
Off
Device not powered – check module status indicator.
Flashing red/green
LED cycle power test present.
Flashing red
Recoverable fault occurred:
• At cycle power the number of expected modules does not equal the number of modules
present
• A module is missing
• Node fault (I/O connection timeout) occurred.
Solid red
Unrecoverable fault occurred – the adapter is bus off.
Flashing green
Firmware (NVS) update in progress.
Solid green
Adapter online with connections established (normal operation,
Run mode).
System Power
Off
Not active; field power is off or DC-DC converter problem present.
Solid green
System power is on; DC-DC converter is active (5V).
Field Power
Off
Not active; field power is off.
Solid green
Power is on; 24V DC is present.
Status Indicators for 1734-AENT Adapter
Indicator
Status
Description