Wire requirements, Wiring recommendation – Rockwell Automation 1764-28BXB MicroLogix 1500 Programmable Controller Base Units User Manual

Page 14

Advertising
background image

14 MicroLogix™ 1500 Programmable Controller Base Units

Publication 1764-IN001B-EN-P

Wire Requirements

Wiring torque = 1.13 Nm (10 in-lb) rated; 1.3 Nm (12 in-lb) maximum

Wiring Recommendation

When wiring without spade lugs, keep the finger-safe covers in place. Loosen the
terminal screw and route the wires through the opening in the finger-safe cover.
Tighten the terminal screw making sure the pressure plate secures the wire.

Table 8 Wire Type Recommendation

Wire Type

Wire Size (2 wire maximum per terminal
screw)

Solid

Cu-90°C (194°F)

#14 to #22 AWG

Stranded

Cu-90°C (194°F)

#14 to #22 AWG

!

ATTENTION

Be careful when stripping wires. Wire fragments that fall into
the controller could cause damage. Once wiring is complete,
be sure the base unit is free of all metal fragments before
removing protective debris strips and installing the processor
unit. Failure to remove strips before operating can cause
overheating.

Finger-Safe Cover