18 MicroLogix™ 1500 Programmable Controller Base Units

Publication 1764-IN001B-EN-P

Table 10 Input Specifications

Description

1764-24AWA

1764-24BWA and 1764-28BXB

Inputs 0 thru 7

Inputs 8 and Higher

On State Voltage
Range

79 to 132V ac

14 to 30.0 V dc at 30°C
(86°F)

14 to 26.4 V dc at 55°C
(131°F)

10 to 30.0 V dc at 30°C
(86°F)

10 to 26.4 V dc at 55°C
(131°F)

Off State Voltage
Range

0 to 20V ac

0 to 5V dc

Operating Frequency

47 Hz to 63 Hz

0 Hz to 20 KHz

(1764-24BWA)

0 Hz to 1 KHz

(1)

(1764-24BWA)

(1) Scan-time dependant.

On State Current:

• minimum

• nominal

• maximum

• 5.0 mA at 79V ac

• 12.0 mA at 120V ac

• 16.0 mA at 132V ac

• 2.5 mA at 14V dc

• 7.3 mA at 24V dc

• 12.0 mA at 30V dc

• 2.0 mA at 10V dc

• 8.9 mA at 24V dc

• 12.0 mA at 30V dc

Off State Leakage
Current

2.5 mA minimum

1.5 mA minimum

Nominal Impedance

12k ohms at 50 Hz

10k ohms at 60 Hz

3.3k ohms

2.7k ohms

Inrush Current (max.)
at 120V ac

250 mA

Not Applicable

Not Applicable

Table 11 Output Specifications

Specification

1764-24AWA/BWA

1764-28BXB

Current per Common

8A

8A

Current per Controller

at 150V Maximum

24A

18A

at 240V Maximum

20A

18A

Table 12 Relay Contact Rating Table 1764-24AWA, -24BWA, -28BXB

Maximum Volts

Amperes

Amperes

Continuous

Voltamperes

Make

Break

Make

Break

240V ac

7.5A

0.75A

2.5A

1800 VA

180 VA

120V ac

15A

1.5A

125V dc

0.22A

(1)

(1) For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing

28 VA by the applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than
48V, the make/break ratings for relay contacts cannot exceed 2A

1.0A

28 VA

24V dc

1.2A

(1)

2.0A

28 VA