Rockwell Automation 1764-28BXB MicroLogix 1500 Programmable Controller Base Units User Manual

Page 20

Advertising
background image

20 MicroLogix™ 1500 Programmable Controller Base Units

Publication 1764-IN001B-EN-P

Table 14 Working Voltage

Specification

1764-L24AWA

Power Supply Input to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation)

Input Group to Backplane Isolation and
Input Group to Input Group Isolation

Verified by one of the following dielectric tests: 151V
ac for 1 second or 2145V dc for 1 second

132V Working Voltage (IEC Class 2 reinforced
insulation)

Output Group to Backplane Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation)

Output Group to Output Group Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation).

Specification

1764-24BWA

Power Supply Input to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation)

Power Supply User 24V Output to
Backplane Isolation

Verified by one of the following dielectric tests: 600V
ac for 1 second or 848V dc for 1 second

50V Working Voltage (IEC Class 2 reinforced
insulation)

Input Group to Backplane Isolation and
Input Group to Input Group Isolation

Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced
insulation)

Output Group to Backplane Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation).

Output Group to Output Group Isolation.

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)

Advertising