MicroLogix™ 1500 Programmable Controller Base Units 21

Publication 1764-IN001B-EN-P

Specification

1764-28BXB

Input Group to Backplane Isolation and
Input Group to Input Group Isolation

Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced
insulation)

FET Output Group to Backplane Isolation
and FET Outputs Group to Group

Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced
insulation)

Relay Output Group to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation)

Relay Output Group to Relay and FET
Output Group Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)

Table 14 Working Voltage