Specifications – Rockwell Automation 1771-ID16 SERIES B Install Instr ac/dc (120V)Isolated Input User Manual

Page 13

Advertising
background image

Specifications

ac/dc (120V) Isolated Input Module

13

Publication 1771-IN070B-EN-P - August 2002

Inputs per Module1

16

Module Location

1771ĆA1B thru ĆA4B or later I/O chassis

1771-AM1, -AM2 Chassis

Input Voltage Range

74-138V ac, 47-63Hz; 105-138V dc

Nominal Input Voltage

120V ac/dc

Nominal Input Current

120V ac: 12.4mA @ 50Hz; 14.9mA @ 60Hz

120V dc: 2.5mA

On-state Voltage (minimum)

74V ac; 105V dc

On-state Current (minimum)

6.0mA @ 74V ac, 47-63Hz

1.2mA @ 105V dc

Off-state Voltage (maximum)

45V ac; 66V dc

Off-state Current (minimum)

4.0mA @ 45V ac, 47-63Hz; 0.8mA @ 66V dc

Input Signal Delay

Off to On

On to Off

0.57ms for ac; 0.57ms for dc

Selectable: 9ms or 18.0ms for ac; Fixed; 9ms for dc

Input Impedance (minimum)

ac: 9.3K ohms @ 47Hz; 6.9K ohms @ 63Hz

dc: 75K ohms off; 48K ohms on

Power Dissipation

7.0 Watts (max.), 0.3 Watts (min.)

Thermal Dissipation

23.8 BTU/hr (max.), 1.0 BTU/hr (min.)

Backplane Current

75mA maximum

Isolation Voltage

Tested to 1500V ac channelĆtoĆchannel for 1s; 1500V ac channel to backplane

for 1s

Maximum Cable Length

1000ft (304.8m)

Conductors Wire Size

Category

Only 14 to 22 gauge (2.5mm

2

to 0.25mm

2

) stranded or solid copper rated at

60

o

or greater

1. 2

3/64 inch (1.2mm) insulation maximum

1

3

Environmental Conditions

Operating

Temperature

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 140

°

F (0

o

to 60

o

C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock)

-40 to 185

°

F (-40 to 85

o

C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5 to 95%, noncondensing

Shock

Operating

Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30g

50g

Vibration

IEC 60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

ESD Immunity

IEC 61000-4-2

4kV contact discharges

Radiated RF Immunity

IEC 61000-4-3

10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

10V/m with 200Hz 50% pulse 100% AMat 900MHz

Specifications continued on next page.

Advertising