Rockwell Automation 1771-ID16 SERIES B Install Instr ac/dc (120V)Isolated Input User Manual
Page 5

Filter Time Jumpers
E1 = Jumper for inputs 00 through 07
E2 = Jumper for inputs 10 through 17
NORM
NORM
FAST
FAST
CH0-7
CH10-17
E1
E2
10557ĆI
ac/dc (120V) Isolated Input Module
5
Publication 1771-IN070B-EN-P - August 2002
To set the filtering time, proceed as follows:
1. Remove the side covers from the module circuit board by
removing the four screws securing the covers to the module and
remove the circuit board.
2. Position the jumpers as required to provide the filter time you
require (see below). Use your fingers to pull the jumper up and
position over the 2 pins corresponding to your selection (Fast or
Norm).
Setting the Filter Time Jumpers
Jumper Position
Time Constant (ms)
Fast (factory default)
9.0 (ac/dc)
Norm
18.0 (ac only)
3. Reinstall the covers on the module circuit board and secure with 4
screws.
Table A
Minimum and Maximum Filter Times
Input
Voltage
Filter Time
(msec)
Off to On (ms)
Minimum
Maximum Typical
On to Off (ms)
Minimum Maximum Typical
ac
9.0
0.5
7.0
2.0
7.0
33
20
ac
18.0
0.5
8.1
2.0
14.0
42
29
dc
9.0
0.7
2.2
1.3
8.3
25
13