ac/dc (120V) Isolated Input Module

14

Publication 1771-IN070B-EN-P - August 2002

EFT/B Immunity

IEC 61000-4-4

+1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5

+1kV line-line (DM) and +2kV line-earth (CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6

10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz

Emissions

CISPR 11

Group 1, Class A (with appropriate enclosure)

Enclosure Type Rating

None (open-style)

Keying

Between 22 and 24

Between 26 and 28

Field Wiring Arm

1771ĆWN

Wiring Arm Screw Torque

9 pound-inches (1.0Nm)

Certifications

(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

CSA

CSA Certified Process Control Equipment for Class I,

Division 2 Group A, B, C, D Hazardous Locations

CE

4

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4, Industrial Emissions

EN 50082-2, Industrial Immunity

EN 61326, Meas./Control/Lab., Industrial Requirements

EN 61000-6-2, Industrial Immunity

European Union 73/23/EEC LVD Directive, compliant with:

EN 61131-2, Programmable Controllers

C-Tick

4

Australian Radiocommunications Act, compliant with:

AS/NZS 2064, Industrial Emissions

1

One or two 14-22 AWG solid or stranded copper wires per terminal. Must be same size. Do not intermix solid and stranded wires. Use

copper wire only

2

14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller wire size may be required.

3

Refer to publication 1770Ć4.1, Industrial Automation Wiring and Grounding Guidelines."

4

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details