Rockwell Automation 1791-16A0 16 INPUT AC BLOCK User Manual

16 input ac block i/o module, Series b, Installation

Advertising
background image

1

1

16 Input AC Block I/O Module

Cat. No. 1791-16A0

Series B

Installation

Mount the block I/O module in a vertical (recommended) or horizontal position.
Allow sufficient room around the block for cooling air flow through the block
module. Refer to Figure 1.

Figure 1
Mounting Dimensions for the Block I/O Module
Cat. No. 1791–16A0 Series B (PLC version shown)

2 mounting holes
for #8 screws

1

30

2.710
(68.8)

1.71

(43.4)

6.95

(176.5)

6.60

(167.6)

0.5

(12.7)

2.0 (50.8) air gap

on all 4 sides.

Block

Operating temperature in air
gap below module must not
exceed 60

o

C (140

o

F).

6.95H x 2.710W x 3.85D
(176.5H x 68.8W x 98D)

Inches

(Millimeters)

Equipment

Grounding Stud

CAUTION: When tightening grounding stud nut, do not exceed 15 in-lbs.

12381–I

1791-16A0