Installation Instructions
Block I/O
Cat. No. 1791-16A0 Series B

4

Figure 5
Wiring Connections with SLC Family Processors (refer to Table A)

RIO

L1

L2/N

L2/N

L1

1

30

SLC

L2/N

L1

GND

COM

1

BLU

CLR

in 00

in 01

in 02

in 03

in 04

in 05

in 06

in 07

COM

1

COM

1

NOT

USED

N

SHD

COM

2

in 08

in 11

in 12

in 13

in 14

in 15

COM

2

NOT

USED

COM

2

in 09

in 10

L1

NOTE: COM 1 connections are internally connected together.

COM 2 connections are internally connected together.

12389–I

The block I/O module has an equipment grounding stud on the lower left side of
the module. Connect this grounding stud to your equipment ground. Torque the
nut to 15 in-lbs maximum when connecting to your equipment ground.

ATTENTION:

Do not overtighten the nut on the grounding stud

when connecting the wire. Damage to the module could result.

Refer to “Programmable Controller Wiring and Grounding Guidelines”
(1770-4.1) for further information.