Rockwell Automation 1791-16A0 16 INPUT AC BLOCK User Manual
Page 11

Installation Instructions
Block I/O
Cat. No. 1791-16A0 Series B
11
11
1791-16A0 Series B Specifications
Input Specifications
Inputs per Block
16 (2 groups of 8)
Nominal Input Current
11.0mA
Nominal Input Voltage
120V ac
On–state Voltage Range
79–132V ac, 47–63Hz
Off-state Voltage
Maximum
35V
On-state Current
Minimum
5mA @ 79V, 60Hz
Off-state Current
Minimum
2.3mA (60Hz)
Input Impedance
Maximum
15K ohms @ 60Hz
Input Signal Delay
Off to on
On to off
1.0ms
26ms (maximum) (allows for 1/2 cycle dropout)
General Specifications
External Power (Internally protected
- no external fuse required)
Voltage
Current
85–132V ac, 47–63Hz
150mA
Dimensions
Inches
Millimeters
6.95H X 2.7W X 3.85D
176.5H X 68.8W X 98D
Isolation
Power supply to RIO
I/O Group-to-Group
I/O Group-to-Logic
500V ac
1250V ac
1250V ac
Power Dissipation
Maximum
8.9 Watts
Thermal Dissipation Maximum
30.35 BTU/hr
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
0 to 60
o
C (32 to 140
o
F)
–40 to 85
o
C (–40 to 185
o
F)
5 to 95% noncondensing
Conductors
Wire Size
Category
14 gauge (2mm
2
) stranded maximum
3/64 inch (1.2mm) insulation maximum
1
1
1
You use this conductor category information for planning conductor routing as described in the
system level installation manual.