Rockwell Automation 1791-16A0 16 INPUT AC BLOCK User Manual
Page 6

SW1
SW2
Open cover to
access switches
1
30
Position = 1
Position = 0
End View of Switch
12391–I
8
7
6
5
4
3
2
1
0
1
8
7
6
5
4
3
2
1
0
1
Default Switch
Settings = 0
NOTE: Set switch SW2–3 to 0 if this rack will have a
unique address (not complemented). If this rack
address is a duplicate of another I/O block or
chassis, set the switch to 1 for primary or 0 for
complementary. Refer to Table C for the
complementary I/O rack address.
1791-16A0
120V ac INPUT
INPUT
INPUT
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
Only block I/O modules with all inputs or
all outputs can use complementary I/O.
ATTENTION: Cycle power to the module after
setting the switches.
Series A block I/O modules do not support
complementary I/O. If using series A
modules, set switch SW2–3 to 0.
Installation Instructions
Block I/O
Cat. No. 1791-16A0 Series B
6
Figure 6
Switch Settings
SW2–8
Not use
Not used
SW2–7
Not used
SW2–6
Last I/O Group
0
Not last rack
1
Last rack
SW2–5
Processor
Restart/Lockout (PRL)
0
Processor Restart
1
Processor Lockout
SW2–4
Hold Last State
0
Reset Outputs
1
Hold Last State
SW2–3
Complementary I/O
1
0
Non-Complemented System
0
Complementary Rack
1
1
Primary Rack
1
1
See note.
Communication Rate
SW2–2
SW2–1
Bits/s
0
0
57.6 K
0
1
115.2 K
1
0
230.4 K
1
1
230.4 K
Starting Quarter
SW1–2
SW1–1
Module
Group
0
0
0 (1st)
0
1
2 (2nd)
1
0
4 (3rd)
1
1
6 (4th)