Rockwell Automation 1791-16A0 16 INPUT AC BLOCK User Manual

Page 6

Advertising
background image

SW1

SW2

Open cover to
access switches

1

30

Position = 1

Position = 0

End View of Switch

12391–I

8

7
6
5

4

3

2
1

0

1

8

7
6
5

4

3

2
1

0

1

Default Switch

Settings = 0

NOTE: Set switch SW2–3 to 0 if this rack will have a

unique address (not complemented). If this rack
address is a duplicate of another I/O block or
chassis, set the switch to 1 for primary or 0 for
complementary. Refer to Table C for the
complementary I/O rack address.

1791-16A0

120V ac INPUT

INPUT

INPUT

00

01
02
03
04
05
06
07

10

11
12
13
14
15
16
17

Only block I/O modules with all inputs or
all outputs can use complementary I/O.

ATTENTION: Cycle power to the module after
setting the switches.

Series A block I/O modules do not support
complementary I/O. If using series A
modules, set switch SW2–3 to 0.

Installation Instructions
Block I/O
Cat. No. 1791-16A0 Series B

6

Figure 6
Switch Settings

SW2–8

Not use

Not used

SW2–7

Not used

SW2–6

Last I/O Group

0

Not last rack

1

Last rack

SW2–5

Processor

Restart/Lockout (PRL)

0

Processor Restart

1

Processor Lockout

SW2–4

Hold Last State

0

Reset Outputs

1

Hold Last State

SW2–3

Complementary I/O

1

0

Non-Complemented System

0

Complementary Rack

1

1

Primary Rack

1

1

See note.

Communication Rate

SW2–2

SW2–1

Bits/s

0

0

57.6 K

0

1

115.2 K

1

0

230.4 K

1

1

230.4 K

Starting Quarter

SW1–2

SW1–1

Module

Group

0

0

0 (1st)

0

1

2 (2nd)

1

0

4 (3rd)

1

1

6 (4th)