Rockwell Automation 1746-XXXX SLC 500 4-Channel Analog I/O Modules User Manual User Manual
Page 20

Publication 1746-UM005B-EN-P - June 2004
2-6 Quick Start for Experienced Users
6.
Configure system I/O configuration.
Reference
Configure your system I/O configuration for the particular slot the analog module is in. When
assigning an I/O module to a slot location, select the module from the displayed list. If not listed,
select OTHER at the bottom of the list and enter the module’s ID code at the prompt.
Chapter 4
(Module
Operation
and System
Considerations)
Catalog No.
Module ID Code
1746-NI4
4401
1746-NIO4I
3201
1746-NIO4V
3202
1746-NO4I
5401
1746-NO4V
5402
7.
Check that the module is operating correctly.
Reference
Chapter 5
(Testing Your
Module)
ATTENTION
Machine motion during system checkout can be
hazardous to personnel. During all checkout
procedures, you must disconnect all devices which,
when energized, might cause machine motion.
Apply power to the fixed or modular system. The analog module LED (red) should be
illuminated, indicating that the module is receiving 24V dc power.