A - specifications, Operating power, Temperature and humidity – Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual
Page 95: Specifications, Appendix, Operating power temperature and humidity

Publication 1747-6.1
Appendix
A
Specifications
This appendix contains the module’s specifications for:
• operating power
• temperature and humidity
• general characteristics
Operating Power
Temperature and
Humidity
Input Line Voltage
18 to 30 V dc
Input Current
104 mA (max) at 24 VDC
Input Volts (ripple)
1V p-p
Input Current Inrush
350 mA pk (max)
Operating Temperature
0 to 55
°
C (+32 to +131
°
F)
Storage Temperature
-20 to +65
°
C (-4 to +149
°
F)
Humidity Rating
5 to 95% (without condensation)
IMPORTANT: Due to the physical properties of
Liquid Crystal Displays, it is important that the
following temperature/humidity ratings be considered
maximums to prevent premature degradation of
display quality:
Temperature Humidity
35
°
C (95
°
F) 95% RH
45
°
C (113
°
F) 85% RH
55
°
C (131
°
F) 75% RH