ControlNet IP67 Tap and Cable Assembly Kit Installation Instructions 13

Publication 1786-IN017B-EN-P - May 2004

e. Inspect the heat-shrink tubing to ensure that there are no voids where the glue has

incompletely melted. Voids could cause a loss of the IP67 rating.

2. Attach the trunk line to the tap. Tighten the trunk-line connector to 1 N-m (0.74

ft.-lbs.).

IMPORTANT

Be sure to install the dust cap on any unused connectors. Doing so will:

prohibit the center conductor or the outer conductor from
inadvertently shorting to ground during installation

provide partial environmental protection if a tap is left disconnected
for a prolonged time

31297-M

Place the tubing against
the shoulder of the TNC
connector

Ensure that there are no
voids where glue has
incompletely melted