Install the Components

1. Determine an adequate mounting location for the tap. Refer to the dimension

drawing shown below.

2. To mount the tap to the DIN rail, use the hardware provided in the kit and attach as

shown in the following illustration.

3. To mount the tap through an enclosure wall, drill a hole of approximately 17.2 mm

for the 1786-TNCJI4 isolated bulkhead connector.

ATTENTION

Do not over-tighten the screws. Over-tightening the screws can
damage the tap. The applied torque should be 0.2-0.4 N-m (1-2
ft.-lbs).

312889-M

2.30 in. (5.8 cm)

1.42 in.
(3.6 cm)

1.21 in.
(3.1 cm)

1.65 in.
(4.2 cm)

Front View

.90 in.
(2.3 cm)

.49 in.
(1.2 cm)

.45 in.
(1.1 cm)

.49 in.
(1.2 cm)

.60 in.

(1.5 cm)

1 in.
(2.5 cm)

Side View

Back View

31287-M

DIN rail

Mount the universal
mounting bracket on the DIN
rails supplied in the kit.