Communicating via the Interface Module
00D5
Incorrect address for the local data table
0500
Message timed out waiting for a response from a client
1000
Illegal command specified in MSG instruction.
2000
Error communicating with a client
3000
Client session has disconnected
4000
Processor connected but faulted (hardware)
5000
Client generated an error converting data.
6000
Requested function is not available. Client’s unsolicited handler
returned an error.
7000
Processor is in program mode
8000
Processor’s compatibility file does not exist
9000
Client’s backlog has been exceeded
B000
Processor is downloading so it is inaccessible
F001
Processor incorrectly converted the address
F002
Incomplete address
F003
Incorrect address
F006
Addressed file does not exist in target processor
F007
Destination file is too small for number of words requested
F00A
Target processor cannot put requested information in packets
F00B
Privilege error, access denied
F00C
Requested function is not available
F00D
Request is redundant
F011
Data type requested does not match data available
F012
Incorrect command parameters
Code
(Hexadecimal - Word 1 of the control block)
Description
(Displayed on the data monitor screen)