D - status led error codes, Ndix d, Status led error codes – Rockwell Automation 1785-ENET USER MANUAL PLC-5 ETHERNET INTERFACE User Manual
Page 49: Appendix, Interpreting led error codes

1785-6.5.19 November 1998
Appendix
D
Status LED Error Codes
Interpreting LED Error Codes
When the status LED blinks red, it signals that a hardware or software
fault has been detected and it reports that error via a code. This code
is a two-digit fault code signalled by a flash sequence. First, the LED
begins the sequence with ten rapid flashes. Then the LED signals the
first digit of the code by a number of slow flashes. Approximately
two seconds after the LED displays the first digit, the LED displays
the second digit. This sequence repeats itself until the module is either
reset or replaced.
Code
Description
01
General 68000 test failure
02
Bus error
03
Address error
04
Illegal instruction
05
Divide by zero
06
CHK instruction
07
TRAPV instruction
08
Privileged instruction
09
Trace trap
10
Line 1010 instruction
11
Line 1111 instruction
12
Hardware breakpoint
13
Coprocessor violation
14
Uninitialized interrupt
15
Format error
16
Autovector interrupts
24
Spurious interrupt
25
TRAP in instruction
26
Unassigned user
27
Unassigned reserved
31
OS area checksum not valid
32
Static RAM self-test failed
33
Jump table wrong