Specifications - ac (120-240V) Output Module, Cat. No. 1771-OAN

Outputs per module

32 (4 groups of 8)

Module Location

1771ĆA1B thru ĆA4B or later 1771 I/O Chassis

Voltage Range

85 to 264V ac, 47Ć63Hz

Nominal Voltage

120/240V ac

Maximum Output Current

Per Point

Per Group

Per Module

1.0A at 30

o

C; Derate linearly to 0.3A at 60

o

C

2.0A at 30

o

C; Derate linearly to 0.6A at 60

o

C

8.0A at 30

o

C; Derate linearly to 2.4A at 60

o

C

Maximum Surge Current

10A for 25ms at 1s intervals at 30

o

C

10A for 25ms at 2s intervals at 60

o

C

Minimum Load Current

10mA per output2

Maximum OnĆstate Voltage Drop

1.5V ac (rms) @ 1A

Maximum OffĆstate Leakage Current

2.3mA per output @ 230V ac, 60Hz

1.2mA per output @ 120V ac, 60Hz

Maximum Output Signal Delay Off to On

On to Off

1.0ms maximum

9.3ms @ 60Hz; 11.0ms @ 50Hz

Power Dissipation

16.2W (max); 1.0W (min)

Thermal Dissipation

55.4 BTU/hr (max); 3.4 BTU/hr (min)

Isolation Voltage

Tested to withstand 1000V for 60s

Backplane Current

800mA maximum @ 5V DC

Environmental Conditions

Operational Temperature

IEC60068-2-1 (Test Ad, Operating Cold)

IEC60068-2-2 (Test Bd, Operating Dry Heat)

IEC60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 140°F (0 to 60°C)

Storage Temperature

IEC60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry

Heat)

IEC60068-2-14 (Test Na, Unpackaged, Nonoperating

Thermal Shock)

-40 to 185°F (-40 to 85°C)

Relative Humidity

IEC60068-2-30 (Test Db, Unpackaged, Nonoperating Damp

Heat)

5 to 95% noncondensing

Shock

Operating

Nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock)

30g

50g

Vibration

IEC60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

ESD Immunity

IEC61000-4-2

4kV contact discharges

Radiated RF Immunity

IEC61000-4-3

10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

10V/m with 200Hz 50% Pulse 100% AM at 900MHz

EFT/B Immunity

IEC61000-4-4

+1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC61000-4-5

+1kV line-line (DM) and +2kV line-earth (CM) on signal ports

Conducted RF Immunity

IEC61000-4-6

10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz