Rockwell Automation 1771-OAN Installation Instructions User Manual

Page 12

Advertising
background image

AC (120/240V) Output Module

12

Publication 1771ĆIN031B-EN-P - November 2002

Specifications - ac (120-240V) Output Module, Cat. No. 1771-OAN

Emissions

CISPR 11

Group 1, Class A (with appropriate enclosure)

Enclosure Type Rating

None (open style)

Keying

Between 16 and 18

Between 22 and 24

Fuses

Four 4.0A, 250V normal blow fuses (1 per group)

Field Wiring Arm

Cat. No. 1771-WN

Field Wiring Arm Screw Torque

7-9 pound-inches (0.7-1.0Nm)

Conductors

Wire Size

Category

14-22AWG (2.5-0.25mm

2

) stranded copper wire rated at 60

o

C

or greater

3/64 inch (1.2mm) insulation (max)

1

1

Certifications

(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

CE

2

European Union 89/336/EECEMCDirective,

compliant with:

EN 61000-6-4, Industrial Emissions

EN 50082-2, Industrial Immunity

EN 61326, Meas./Control/Lab., Industrial

Requirements

EN 61000-6-2, Industrial Immunity

European Union 73/23/EECLVD Directive,

compliant with:

EN 61131-2, Programmable Controllers

C-Tick

2

Australian Radiocommunications Act,compliant

with AS/NZS 2064, Industrial Emissions

1 Use this conductor category information for planning conductor routing . Refer to publication 1770Ć4.1, Industrial Automation Wiring and

Grounding Guidelines."

2 See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1771ĆIN031B-EN-P - November 2002

Supersedes publication 1771Ć5.31 - October 1995

PN957678-75

Copyright 2002 Rockwell Automation, Inc. Printed in USA

Advertising