Rockwell Automation 1771-OAN Installation Instructions User Manual
Page 9

AC (120/240V) Output Module
9
Publication 1771ĆIN031B-EN-P - November 2002
Table A
Module Output Terminal Assignments
Terminal
Number
Output Assignment
I/O program address
Terminal
Number
Output Assignment
I/O program address
01
1
120V ac
Ć
21
1
120V ac
Ć
02
Output 00
0RG00
22
Output 00
0R(G+1)00
03
Output 01
0RG01
23
Output 01
0R(G+1)01
04
Output 02
0RG02
24
Output 02
0R(G+1)02
05
Output 03
0RG03
25
Output 03
0R(G+1)03
06
Output 04
0RG04
26
Output 04
0R(G+1)04
07
Output 05
0RG05
27
Output 05
0R(G+1)05
08
Output 06
0RG06
28
Output 06
0R(G+1)06
09
Output 07
0RG07
29
Output 07
0R(G+1)07
10
N.C.
Ć
30
N.C.
Ć
11
1
120V ac
Ć
31
1
120V ac
Ć
12
Output 10
0RG10
32
Output 10
0R(G+1)10
13
Output 11
0RG11
33
Output 11
0R(G+1)11
14
Output 12
0RG12
34
Output 12
0R(G+1)12
15
Output 13
0RG13
35
Output 13
0R(G+1)13
16
Output 14
0RG14
36
Output 14
0R(G+1)14
17
Output 15
0RG15
37
Output 15
0R(G+1)15
18
Output 16
0RG16
38
Output 16
0R(G+1)16
19
Output 17
0RG17
39
Output 17
0R(G+1)17
20
N.C.
Ć
40
N.C.
Ć
Where:
R = rack number (1, 2, 3, etc.)
G = I/O group (0 Ć 7)
G+1 = I/O group plus 1
Note: If multiple power supplies are used, do not exceed the specified isolation voltage.
1
For operating voltages greater than 120V ac, each channel group must be connected to the same operating voltage phase at L1.