Rockwell Automation 1771-OAN Installation Instructions User Manual

Page 4

Advertising
background image

AC (120/240V) Output Module

4

Publication 1771ĆIN031B-EN-P - November 2002

The 1771-OAN ac output module is a source output and requires a
sink input. A sink input provides a path to ground and a source
output provides a positive voltage path.

This module is not compatible with 2-slot addressing. You must use
1-slot addressing with restrictions, or 1/2-slot addressing with no
restrictions.

IMPORTANT

You must use this module in a 1771-A1B thru
-A4B or later 1771 I/O chassis. Refer to the
Table below for processor compatibility.

Processor Compatibility Chart

System Type

Use with Processors:

Local

MiniĆPLCĆ2/02 (cat. no. 1772ĆLZ, ĆLZP)

MiniĆPLCĆ2/16 (cat. no. 1772ĆLX, ĆLXP)

MiniĆPLCĆ2/17 (cat. no. 1772ĆLW, ĆLWP)

PLCĆ5/15, Series B and later (cat. no. 1785ĆLT)

Remote (with a 1771ĆASB remote

I/O adapter)

PLCĆ2/20 (cat. no. 1772ĆLP2)

PLCĆ2/30 (cat. no. 1772ĆLP3)

PLCĆ3 (cat. no. 1775ĆL1, ĆL2, ĆL3, ĆL4)

PLCĆ3/10 (cat. no. 1775ĆLP4, ĆLP8)

PLCĆ5/15, Series B and later (cat. no. 1785ĆLT)

Do not place this module in the same I/O chassis as the 1771-IX
thermocouple module. You can use this module in the same chassis
as the 1771-IXE thermocouple module.

The controller or I/O chassis power supply, connected through the
backplane of the I/O chassis, powers the logic circuitry of the output
modules. The maximum current drawn from this supply is 800mA.

PreĆinstallation

Considerations

Power Supply

Requirements