18 ControlLogix-XT EtherNet/IP Bridge Module

Publication

1756-IN635A-EN-P - March 2009

Status Indicators

Use these tables to interpret the status indicators.

NET Status Indicator

State

Description

Off

The module is not powered. Verify that there is chassis power and
that the module is completely inserted into the chassis and
backplane.

The module does not have a valid IP address. Make sure the module
has been configured with a valid IP address.

Flashing green

The module has an IP address, but has no established connections.

Green

The module has an IP address and at least one established
connection.

Flashing red

One or more of the connections in which the module is the target has
timed out.

Red

The module is attempting to use an IP address already in use on the
network. Assign a unique IP address to the module.

LNK Status Indicator

State

Description

Off

The module is not ready to communicate. Verify that the
module is on.

Green

The module is ready to communicate.

Flashing green

The module is communicating over the network.