Specifications

AC (120V) Input Module

11

Publication 1771-IN032B-EN-P - July 2002

Inputs per module

32 (4 groups of 8)

Module Location

1771-A1B thru -A4B I/O Chassis

Voltage Range

85 to 135V ac, 50/60Hz

Nominal Input Voltage

120V ac

Nominal Input Current

8.2mA @ 115V ac, 60Hz

6.8mA @ 115V ac, 50Hz

Minimum On-state Current

5.2mA @ 85V ac, 60Hz

4.2mA @ 85V ac, 50Hz

Maximum Off-state Current

2.3mA @ 30V ac, 60Hz

1.9mA @ 30V ac, 50Hz

Maximum Off-state Voltage

30V ac

Input Impedance

0.2uF in parallel with 200K ohms (13.3K ohms @ 60Hz)

Input Signal Delay

Off to On: 10.0ms (+7ms)

On to Off: 20.0ms (+15ms)

Isolation Voltage

Testedto withstand 1000V for 60s.

Power Dissipation

4.5W (max); 1.0W (min)

Thermal Dissipation

15.4 BTU/hr (max); 3.4 BTU/hr (min)

Backplane Current

280mA @ 5V dc maximum

Conductors

Wire Size

Category

14-22 AWG (2.5-0.25mm

2

) (max)

1

stranded copper rated at

60

o

or greater

3/64 inch (1.2mm) insulation (max)

2

1

Environmental Conditions

Operating

Temperature

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 140°F (0

o

to 60

o

C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal

Shock)

-40 to 185°F (-40 to 85

o

C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp

Heat)

5 to 95%, noncondensing

Shock

Operating

Nonoperating

IEC 60068-2-27 (Test Ea, UnpackagedShock)

30g

50g

Vibration

IEC 60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

ESD Immunity

IEC 61000-4-2

4kV indirect discharges

Radiated RF Immunity

IEC 61000-4-3

10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4

+1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5

+1kV line-line (DM) and+2kV line-earth (CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6

10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz