Rockwell Automation 1771-IAN 120V Input Module Installation Instructions User Manual

Page 12

Advertising
background image

AC (120V) Input Module

12

Publication 1771-IN032B-EN-P - July 2002

Emissions

CISPR 11

Group 1, Class A (with appropriate enclosure)

Enclosure Type Rating

None (open-style)

Keying

Between 16 and18

Between 20 and22

FieldWiring Arm

1771ĆWN

Wiring Arm Screw Torque

9 pound-inches (1.0Nm)

Certifications

(when product is marked)

UL

UL ListedIndustrial Control Equipment

CSA

CSA CertifiedProcess Control Equipment

CSA

CSA CertifiedProcess Control Equipment for Class I,

Division 2 Group A, B, C, D Hazardous Locations

CE

3

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4, Industrial Emissions

EN 50082-2, Industrial Immunity

EN 61236, Meas./Control/Lab., Industrial

Requirements

EN 61000-6-2, Industrial Immunity

European Union 73/736/EEC EMC Directive,

compliant with:

EN 61131-2, Programmable Controllers

C-Tick

3

Australian Radiocommunications Act, compliant with:

AS/NZS 2064, Industrial Emissions

1

14 gauge wire connectedto all terminals may not allow the cover on the fieldwiring arm to close. A smaller gauge wire may

be used.

2

You use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Industrial

Automation Wiring and Grounding Guidelines.

3

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details

Publication 1771-IN032B-EN-P - July 2002

Supersedes Publication 1771-5.32 - October 1995

PN957678-76

Copyright 2002 Rockwell Automatiion, Inc. Printedin USA