Rockwell Automation 1771-IAN 120V Input Module Installation Instructions User Manual

Page 9

Advertising
background image

AC (120V) Input Module

9

Publication 1771-IN032B-EN-P - July 2002

Table A

Module Input Terminal Assignments

Terminal

Number

Input Assignment

I/O program address

Terminal

Number

Input Assignment

I/O program address

01

Input 00

1RG00

21

Input 00

1RG00

02

Input 01

1RG01

22

Input 01

1RG01

03

Input 02

1RG02

23

Input 02

1RG02

04

Input 03

1RG03

24

Input 03

1RG03

05

Input 04

1RG04

25

Input 04

1RG04

06

Input 05

1RG05

26

Input 05

1RG05

07

Input 06

1RG06

27

Input 06

1RG06

08

Input 07

1RG07

28

Input 07

1RG07

09

Common 0 (L2)

1

-

29

Common 3 (L2)

1

-

10

Common 0 (L2)

1

-

30

Common 3 (L2)

1

-

11

Input 10

1RG10

31

Not used

1RG10

12

Input 11

1RG11

32

Input 11

1RG11

13

Input 12

1RG12

33

Input 12

1RG12

14

Input 13

1RG13

34

Input 13

1RG13

15

Input 14

1RG14

35

Input 14

1RG14

16

Input 15

1RG15

36

Input 15

1RG15

17

Input 16

1RG16

37

Input 16

1RG16

18

Input 17

1RG17

38

Input 17

1RG17

19

Common 1 (L2)

1

-

39

Common 4 (L2)

1

-

20

Common 1 (L2)

1

-

40

Common 4 (L2)

1

-

Where:

R = rack number (1, 2, 3, etc.)

G = I/O group (0 - 7)

1

You can connect a different power supply to each common (0,1,2 and 3). Terminals 09/10 are common for terminals 01 thru 08;

19/20 for 11 thru 18; 29/30 for 21 thru 28; 39/40 for 31 thru 38. If multiple power supplies are used, do not exceed the specified

isolation voltage.

Advertising