Rockwell Automation 1792D-8BT0LP ArmorBlock LP2 8 Sinking Input Module User Manual
Page 6

6
ArmorBlock LP2 8 Sinking Input Module
Publication 1792D-5.47 - August 1999
Change of state - productions occur when an input changes or a fault
condition occurs. If no input or fault condition change occurs within the
expected packet rate, a heartbeat production occurs. This heartbeat
production tells the scanner module that the I/O module is alive and ready
to communicate. Consumption occurs when data changes and the master
produces new input data to the I/O block.
Refer to the table below for the word/bit definitions.
The DeviceNet Network uses advanced network technology, producer/
consumer communication, to increase network functionality and
throughput. Visit our web site at http://www.ab.com/networks for producer/
consumer technology information and updates.
Bit
07
06
05
04
03
02
01
00
Produces 0
I7
I6
I5
I4
I3
I2
I1
I0
Produces 1
ISC
RSVD
RSVD
RSVD
RSVD
RSVD
RSVD
RSVD
Where: I= Input
ISC=Input Short Circuit
RSVD = Reserved
Byte
Bit
Description
Produces 0
00-07
Input status bits: When the bit is set (1), the input is on. Bit
00 = input 0, bit 01= input 1, bit 02 = input 2, bit 03 =
input 3, bit 04 = input 4, bit 05 = input 5, bit 06 = input 6,
bit 07 = input 7.
Produces 1
07
Input Short Circuit