Rockwell Automation 1792D-8BT0LP ArmorBlock LP2 8 Sinking Input Module User Manual
Page 8
Advertising
![background image](/manuals/579956/8/background.png)
8
ArmorBlock LP2 8 Sinking Input Module
Publication 1792D-5.47 - August 1999
The following table describes the network status indicator
.
The following table describes I/O status indicators.
For more information on indicators, see the Product Data publication
1792-2.1.
Network Status Indicator
Indication
Status
None
Not On-line
Green
Blinking
Solid
On-line/No Connections
On-line/Connected
Red
Blink
Solid
Connection Timed Out
Failed Communication: A duplicate node address exists or
module is at the wrong baud rate.
I/O Status Indicators
Function
Module Status Indicator
Point Indicator
Condition
Inputs
Green
Green
Blinking Red
None
Yellow
None
No valid input
Valid input
Input Short