Communicate With Your ArmorBlock MaXum I/O Module

This ArmorBlock module’s I/O is exchanged with the master through
a cyclic, poll, or change-of-state connection.

The module consumes and produces I/O data as follows:

Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O
message to the module. The 12 input / 4 output module consumes
the message, updates outputs, and produces a response. The
response has input data, input faults, output faults, and the status of
the auxiliary power.

Change-of-State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the
I/O module is alive and ready to communicate. Consumption occurs
when data changes and the master produces new output data to the
I/O block.

Refer to the table below for the word/bit definitions.

Type of I/O Connections

Consumes

Produces

Cyclic

1 Byte

4 Bytes

Polled

1 Byte

4 Bytes

Change-of-State

1 Byte

4 Bytes

Bit

07

06

05

04

03

02

01

00

Produces 0

I7

I6

I5

I4

I3

I2

I1

I0

Produces 1

ISC-D

ISC-C

ISC-B

ISC-A

I11

I10

I9

I8

Produces 2

OW-F

OW-E

OW-D

OW-C

OW-B

OW-A

ISC-F

ISC-E

Produces 3

RSVD

OPWR

RSVD

RSVD

OFLT3

OFLT2

OFLT1

OFLT0

Consumes 0

RSVD

RSVD

RSVD

RSVD

O3

O2

O1

O0

Where: I = Input, ISC = Input Short Circuit in Sensor Source Voltage, OW = Off Wire,

RSVD = Reserved, OPWR = Output Power (auxiliary power), OFLT = Output fault, O = Output