4 ArmorBlock MaXum 12 Input/ 4 Output Module With Ground Lug

Publication

1792D-IN056A-EN-P - October 2004

Install Your ArmorBlock MaXum I/O Module

To install the module you must:

• Set the node address

• Mount the module to the cable base

• Connect the input/output cord sets to the MaXum module

• Communicate with your ArmorBlock MaXum I/O module

Each of these steps is explained in the following procedures.

Set the Node Address

Valid node addresses are 00 through 63.

Set the node address using the rotary switches, RSNetWorx for
DeviceNet, or another software configuration tools. Setting the
switches to a number from 64 through 99 lets the software have
address control.

Each module is shipped set for node address 63. The switches are
located on the underside of the module. The two switches are:

• MSD (most significant digit)

• LSD (least significant digit)

ATTENTION

Preventing Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:

• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• If available, use a static-safe workstation.
• When not in use, store the equipment in appropriate static-safe

packaging.