3Ć1

3.0 INSTALLATION

This section describes how to install and remove the module and its

cable assembly.

3.1

Wiring

The installation ofwiring should conform to all applicable codes.
To reduce the possibility ofelectrical noise interfering with the proper

operation ofthe control system, exercise care when installing the

wiring from the system to the external devices. For detailed

recommendations refer to IEEE 518.

3.2

Initial Installation

Use the following procedure to install the module:
Step 1.

Turn off power to the system. All power to the rack as well

as all power to the wiring leading to the module should be

off.

Step 2.

Mount the terminal strip (M/N 57C370, 61C505, or

61C506) on a panel. The terminal strip should be

mounted to permit easy access to the screw terminals on

the terminal strip. Make certain that the terminal strip is

close enough to the rack so that the cable will reach

between the terminal strip and the module.

Step 3.

Fasten field wires to the terminal strip. Note that the bit

number and wire number are not the same. Typical field

signal connections are shown in figure 3.1. Refer to

Appendix C for the arrangement of terminal strip

connections. Make certain that all field wires are securely

fastened.