background image

3Ć4

rack be rotated one position to the right of the keys on the

preceding module.
If you use this method, the keys on a particular connector

will be positioned in such a way as to fit together only with

a specific module, and there will be little chance of the

wrong connector being attached to a module.

Step 8.

Turn on power to the system.

Step 9.

Verify the installation by connecting the programming

terminal to the system and running the ReSource

Software.
Stop all programs that may be running.
Use the I/O MONITOR function. If the module is in a local

rack, enter the module slot number and register

(always 0).
If the module is in a remote rack, enter the slot number of

the master remote I/O module, remote I/O drop number

(also called the remote rack number), output module slot

number, and register (always 0).
One at a time, toggle each of the bits that have been wired

to output devices to verify that the installation has been

completed correctly.

WARNING

BE CAREFUL WHEN WRITING TO THE OUTPUTS TO INSURE THAT NO

UNEXPECTED MACHINE MOTION WILL RESULT. FAILURE TO OBSERVE THIS

PRECAUTION COULD RESULT IN BODILY INJURY OR DAMAGE TO EQUIPMENT.

3.3

Module Replacement

Use the following procedure to replace a module:
Step 1.

Turn off power to the rack and all connections.

Step 2.

Use a screwdriver to loosen the screws holding the

connector to the module. Remove the connector.

Step 3.

Loosen the screws holding the module to the rack.

Remove the module from the slot in the rack.

Step 4.

Place the module in the antiĆstatic bag it came in, being

careful not to touch the connectors on the back of the

module. Place the module in the cardboard shipping

container.

Step 5.

Take the new module out of the antiĆstatic bag, being careful

not to touch the connectors on the back of the module.

Step 6.

Insert the module into the desired slot in the rack. Use a

screwdriver to secure the module into the slot.

Step 7.

Attach the field terminal connector (M/N 57C370, 61C505,

or 61C506) to the mating half on the module. Make certain

that the connector keys are oriented correctly and that the

connector is the proper one for this module (see step 7 in

3.2 Initial Installation). Use a screwdriver to secure the

connector to the module.

Step 8.

Turn on power to the rack.