Ladder logic and control block tasks read inputs once at the

beginning of each scan and write outputs once at the end of each

scan. BASIC tasks read an input and write an output for each

reference throughout the scan.

4.3.1

Ladder Logic Task Example

RUN

STARTPL

light

1050

RUN

The symbolic names RUN and STARTPL reference the output modules

that were defined in the configuration. The trailing at symbol @" is not

used in ladder logic tasks. The symbolic name light" is local to the

ladder logic task and does not have I/O associated with it.

4.3.2

BASIC Task Example

1000

LOCAL LIGHT@

\!Fault light

1010

COMMON STARTPL@

\!Start Command

2000

COMMON RUN@

\!Line run

3000

!

4000

!

5000

RUN@ = NOT LIGHT@ AND ( STARTPL@ OR

RUN@)

5500

!

6000

END

The symbolic names RUN@ and STARTPL@ reference the output

modules that were defined in the configuration. The symbolic name

LIGHT@ is local to the BASIC task and does not have I/O associated

with it.

4.3.3

Control Block Task Example

2400

COMMON STARTPL@

\!Start command

2500

LOCAL MOMENTARY@

\!Momentary output

3000

!

4000

!

5000

CALL TRANSITION( INPUT=MOMENTARY@,

OUTPUT=STARTPL@)

5500

!

6000

END

The symbolic name STARTPL@ references the output module that

was defined in the configuration. The symbolic name

MOMENTARY@ is local to the control block task and does not have

I/O associated with it.