Chapter 8 Create Alarms

Follow These Steps

Complete these steps to create alarms for the sample application.

Review Application Alarms

The speed of the motor in the sample application ranges from 0 to 1000 rpm. The tag that controls the speed
of the motor is MOTOR_SPEED. Two numeric alarms will alert you when the motor reaches its ideal
operating speed and when the speed nears its upper threshold.

• The first alarm is triggered when the value at the Motor_Speed tag rises to 850 or above. When the

alarm is triggered, the alarm banner opens and displays the message MOTOR AT IDEAL
OPERATING SPEED!

• The second alarm is triggered when the value at the Motor_Speed tag rises to 900 or above. When the

alarm is triggered, the alarm banner opens and displays the message MOTOR SPEED NEAR
THRESHOLD!

Application alarms

Trigger Tag

Alarm Type

Edge Detection Value

Deadband

Level

Deadband

Mode

Message

Motor_Speed

Numeric

Rising

850

0

Percent

MOTOR AT IDEAL

OPERATING

SPEED!

Motor_Speed

Numeric

Rising

900

0

Percent

MOTOR SPEED

NEAR

THRESHOLD!