1000 terminals – Rockwell Automation 2711P-RY2032 Battery Replacement Installation Instructions User Manual
Page 7

Battery Replacement 7
Rockwell Automation Rockwell Automation Publication 2711P-IN009F-EN-P - July 2014
Replace Battery in PanelView Plus 6 Compact Terminals
1000 Terminals
Follow these steps to replace the battery in a 1000 terminal.
1. Disconnect power from the terminal.
2. Place the terminal, display side down, on a flat stable surface.
3. Detach the communication module, if attached, from the logic module by removing the
four screws.
4. Loosen the four captive screws that attach the logic module to the display.
5. Carefully lift the logic module away from the terminal and turn over to expose the circuit
board.
6. Locate the battery on the circuit board.
7. Remove the battery by lifting up the side of the battery.
8. The battery can be removed up to 15 seconds without losing clock and calendar data.
9. Insert the new battery.
10. Reattach the logic module by aligning the two connectors on the bottom of the logic
module with the connectors on the back of the display module.
Communication Module
Display Module
Captive Screw
Screw
Logic Module