6 Industrial Integrated Display Computers with Keypad

Rockwell Automation Publication 6180P-IN001C-EN-P - July 2013

Mounting Clearances

Allow adequate space around the computer for mounting, air flow, connections, and
maintenance. Sufficient airflow throughout the system unit is required to maintain proper
cooling. Clearance should be enough to allow convenient installation or removal of peripheral
components, such as the optical disc drive.

Panel Mounting Guidelines

Observe these guidelines when installing the unit in a panel:

Confirm that there is adequate space within the panel enclosure.

Cut supporting panels to specifications before installation.

Take precautions so metal cuttings do not enter components already installed in panel.

Supporting panels must be at least 14 gauge to ensure proper sealing against water and
dust, and to provide proper support. The mounting hardware supplied accommodates
panels up to 6 mm (0.24 in.) thick.

Remove all electrical power from the panel before making cutout.

Make sure the area around the panel cutout is clear.

IMPORTANT

Use adequate ventilation or other cooling methods to maintain the product temperature at its
specified rating.

ATTENTION: Failure to follow these guidelines may result in personal injury or damage to the
panel components.

Top: 50 mm (2 in.) for air flow

Left: 50 mm (2 in.) for air flow

Back:
25 mm (1 in.) for air flow
178 mm (7 in.) for drive access

Bottom:
102 mm (4 in.)
for air flow and
connections

Right: 76.2 mm (3 in.) for air flow