Power wiring diagram – Rockwell Automation 2092-DAx Ultra1500 Digital Servo Drive Quick Start User Manual

Page 4

Advertising
background image

4 Ultra1500 Digital Drives Quick Start

Publication 2092-QS001D-EN-P — July 2005

Figure 4

Dimensional Outline Drawing for 2092-DA4 and 2092-DA5

Power Wiring Diagram

63.0

(2.48)

27.0

(1.06)

5.0

(0.20)

5.0

(0.20)

145.0
(5.70)

Mounting hole (top) and slot
(bottom) require M5 x 10 bolts

Chassis ground
terminals (2)

12.0

(0.47)

185.0
(7.28)

198.0
(7.80)

55.0

(2.17)

155.0
(6.10)

90.0

(3.54)

Dimensions are in millimeters (inches). Drives are designed to metric dimensions; inches are a mathematical conversion.

11. Refer to manual included with motor for power, feedback, and brake interconnect information (pinouts and/or wire colors).
12. Wire sizes are minimum recommended values. Local regulations should be observed.

MOTOR

MOTOR POWER WIRES U, V, W, AND GND

MOTOR POWER
MATING CONNECTOR
CONTACT SIZE

TL-SERIES 2.5 mm (14 AWG)

2

MINIMUM
RECOMMENDED
POWER WIRE SIZE
(75 C COPPER)

O

2.5 mm (14 AWG)

2

TERMINAL STRIP ACCEPTABLE WIRE RANGES

0.8 - 2.5 mm (28 - 12 AWG)

2

PIN

SIGNAL

A

B

C

U

V

W

D

MOTOR POWER

CONNECTOR

MOTOR CASE

(GROUND)

INPUT POWER WIRES

2092-DA1 L1, L2, L1C, L2C, GND

2.5 mm (14 AWG)

2

2092-DA2

2.5 mm (14 AWG)

2

2092-DA3

2.5 mm (14 AWG)

2

2092-DA4

2.5 mm (14 AWG)

2

2092-DA5

2.5 mm (14 AWG)

2

DRIVE

TERMINALS

MINIMUM
RECOMMENDED
POWER WIRE SIZE
(75 C COPPER)

O

L1, L2, L1C, L2C, GND

L1, L2, L1C, L2C, GND

L1, L2, L3, L1C, L2C, GND

L1, L2, L3, L1C, L2C, GND

DIGITAL DRIVE MODULE INPUT CURRENT REQUIREMENTS

DRIVES

2092-DA1

2092-DA2

2092-DA3

2092-DA4

TERMINALS

L1, L2, GROUND

L1, L2, GROUND

L1, L2, GROUND

L1, L2, L3, GROUND

MAXIMUM
CURRENT REQUIREMENT,
(AMPS, AC RMS)

3.3 AMPS AC at 200-240 VOLTS AC

5.5 AMPS AC at 200-240 VOLTS AC

8.0 AMPS AC at 200-240 VOLTS AC

11.0 AMPS AC at 200-240 VOLTS AC

2092-DA5 L1, L2, L3, GROUND 15.0 AMPS AC at 200-240 VOLTS AC

ALL

L1C, L2C

2.0 AMPS AC at 200-240 VOLTS AC

6. High-frequency grounding, using heavy braided wires, should connect together the electronic equipment, electrical enclosure, machine frame, and motor housing.

5. Internal shunt resistor is present only on 2092-DA3, 2092-DA4, and 2092-DA5 drives. B1 and B2 should be left disconnected on 2092-DA1 and 2092-DA2 drives.

3. Isolation transformer is optional. If used, the secondary of the transformer must be grounded.

10. 2092-DA1 and 2092-DA2 drives have one grounding screw on the heatsink. 2092-DA3, 2092-DA4, and 2092-DA5 drives have two grounding screws on the heatsink.

8. 2092-DA1, 2092-DA2, and 2092-DA3 drives are single-phase AC input drives; input power is not connected to L3 on these drives. .

Notes:

7. If the power factor or harmonic distortion needs improvement, the jumper from P1 to P2 can be replaced with an inductor.

9. DC Bus Voltage connection - not an AC power input.

2. If using an isolation transformer, ensure the phase to neutral/ground voltage does not exceed the input ratings of the drive.

1. A supply disconnecting device is required for maintenance and safety. Local regulations should be observed.

4. AC line filter and shielded motor cable are to be used for improving the drive module's electromagnetic compatiblity (EMC), and are required to meet European EMC directive.

Wiring between the drive module and filter should be kept as short as possible. The common ground bus bar should be as close to the drive as possible.

CAUTION: AC line filters have large leakage currents and require discharge time upon power removal.

Tighten the ground terminal screw(s) to 1.25 Nm (11 lbs-in.)

L1

ULTRA1500

L2

L3

L1C

L2C

N

P1

P2

B1

B2

M1

AC

LINE

FILTER

SHUNT

RESISTOR

U

V

W

MOTOR

FUSE

BLOCK

1:1 ISOLATION

TRANSFORMER

FUSED

DISCONNECT

OR CIRCUIT

BREAKER

230V

3-PHASE

AC LINE

50/60 HZ

DRIVES

2092-DA1
2092-DA2
2092-DA3
2092-DA4
2092-DA5

2

8

4

7

3

5

9

6

1

10

11

GROUND BAR

6