Rockwell Automation 2706-PxM_PxK_PxP InView Communication Module Installation User Manual

Page 10

Advertising
background image

10 InView Communication Modules

Publication 2706-IN015E-EN-P - May 2007

Using the Communication Module with a 2706-P22R Display

The 2706-P22R InView panel-mount display can be used with a 2706-PxP
communication module. The module is mounted on a DIN rail inside the enclosure
in which the 2706-P22R display is mounted. This maintains the NEMA 4x, 12, or 13
rating. The 2706-PxP communication module also requires a separate 24V dc power
supply. This module does not receive power from the InView display.

Follow these steps to mount and connect the communication module.

1. Disconnect power to the enclosure.

2. Mount the DIN rail somewhere in the enclosure, near the 2706-P22R display.

3. Snap the communication module to the DIN rail and lock the latches.

4. Connect the user-supplied network cable to the communication module.

ATTENTION

Hazardous voltage. Contact with high voltage may cause death or serious
injury. Always disconnect power to the InView display prior to servicing.

1

2

3

4

5

6

7

8

9

RS-232

1

2

3

4

5

6

7

8

9

RS-232

24V dc
(user-supplied)

DIN Rail

To Controller
(user-supplied cable)

2706-NC13 Serial Cable (supplied)

24V dc

Class 2
24V dc

Network Port

Advertising