2. Open the front of the InView display case by turning the latches counter
clockwise and carefully lowering (opening) the front of the case.
3. Install the communication module to the mounting plate located near the
TB1 terminal block by using the supplied standoffs and screws.
4. Torque the screws to 0.68 Nm (6 lb-in).
Wire the Communication Module to the 2706-P72 and 2706-P74 Displays
The power to the communication module is provided by the InView display
(series C).
Follow these steps for wiring the communcation module.
1. Connect the serial wires to the TB1 terminal block in the InView display.
ATTENTION
A label is included in the hardware kit that indicates the default IP address for
the 2706-PENETK EtherNet/IP communication module. The module is shipped
with a default IP address of 192. 168. 1.1. Please consult with personnel who
will be configuring communication for the most appropriate placement of the
label.
TIP
The 2706-PxK communication modules are powered through the serial cable by
the display (series C).
TB1
To TB1
To Controller
(user-supplied
cable)
Black (GND)1
Red (PWR, +5V)2
Orange (TX)3
Brown (RX)4
5
6
7
8
Serial Wires
TB1