Install the card, Prevent electrostatic discharge, Set the node address – Rockwell Automation 1799-D10U10VZC Zone Control I/O Cards  User Manual

Page 5

Advertising
background image

Zone Control I/O Cards 5

Publication 1799-IN007D-EN-P - October 2005

Install the Card

To install the card:

• Set the node address
• Mount the card (brackets, mounting plate)
• Connect the card (DeviceNet network, auxiliary power, I/O)
• Communicate with your card
• Configure the parameters

More detailed information about each of these steps is in the following procedures.

Prevent Electrostatic Discharge

Set the Node Address

Valid node addresses are 00 to 63.

Set the node address using the rotary switches or a DeviceNet configuration tool such as
RSNetWorx for DeviceNet software. Setting the switches between 64 and 99 lets the software
have address control.

ATTENTION

This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:

• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• If available, use a static-safe workstation.
• When not in use, store the equipment in appropriate static-safe

packaging.

IMPORTANT

You must use RSNetWorx for DeviceNet software, revision 3.21 or later
with the Zone Control I/O cards.