FLEX Ex Power Supply 11

Publication

1797-5.12 - June 2010

Table 2 Environmental Specifications

Table 3 Certifications

Dimensions (HxWxD) approx. 140 x 174 x 174 mm

(5.51 x 6.9 x 6.9 in.)

Protections class

IP 66/NEMA 7B

Weight (approx.)

7.3 kg (16 lb)

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…70 °C (-4…158 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp
Heat):
5…95% noncondensing

Shock

Operating

Nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock):

15 g
15 g

Vibration

IEC60068-2-6 (Test Fc, Operating):

2 g @ 10…500 Hz

Emissions

CISPR 11

Radiated, Class A
Conducted, Class B

Certifications (when
product is marked)

(1)

Value

UL, C-UL

Associated Apparatus, Class I, Zone 1, AEx ib IIC T4.

Providing intrinsically safe circuits for use in Class I, Zone 0,
Group IIC Hazardous Locations when installed per
Allen-Bradley Control Drawing No. 1797-6.5.6.
Associated Apparatus, Class I, Groups A, B, C and D;

Class II, Groups E, F and G; Class III Hazardous Locations.

Providing intrinsically safe circuits for use in Class I, Groups
A, B, C and D; Class II, Groups E, F and G; and Class III
Hazardous Locations when installed per Allen-Bradley Control
Drawing No. 1797-6.5.6.