16 FLEX Ex Power Supply
Publication
1797-5.12 - June 2010
FM I/O Entity Parameters
If this product has the FM mark, it has been designed, evaluated, tested, and
certified to meet the following standards:
FM Cl. No. 3600
FM Cl. No. 3610
FM Cl. No. 3615
FM C1 No. 3810
ANSI/NEMA-250
Wiring Methods
Wiring method 1 - Each channel is wired separately.
Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC).
Table 5
Wiring
Method
Channel
Terminals
V
oc
(V) I
sc
(A)
Group
C
a
(
F)
L
a
(
H)
1 and 2
Any one
channel (for
example, ch1)
10(+), 11(-)
9.5
1.0
A, B
0.5
8
C, E
1.5
24
D, F, G
4.0
64