Rockwell Automation 1797-PS2N2 FLEX Ex Power Supply User Manual
Page 14

14 FLEX Ex Power Supply
Publication
1797-5.12 - June 2010
WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a
system when the approved values of V
oc
and I
sc
of the associated apparatus
are less than or equal to V
max
and I
max
of the intrinsically-safe apparatus and
1 and 2
Any one
channel (for
example, ch1)
11(+), 10(-)
9.5
1.0
A, B, IIC
0.5
8
C, E, IIB
1.5
32
D, F, G, IIA
4.0
64
11
1 2 3 4 5
17
16
15
14
13
12
11
10
Ch4
Ch3
Ch2
Ch1
Nonhazardous
Location
Hazardous (Classified) Location
1797-PS2N2
Class I, Division 1, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class III
Input
Power
Nonintrinsically
Safe
Wiring
Intrinsically
Safe Wiring
42101
To any IS device
with entity concept
parameters of
(V
max
, I
max
, C
i
, L
i
)
appropriate for
connection to
associated
apparatus with
entity concept
parameters listed
in Table 3.
12
11