4 FLEX Ex Power Supply

Publication

1797-5.12 - June 2010

Features include the following:

 24V dc supply source
 Four channels, 8.5 W output each channel
 Dual power feeds for source input redundancy
 Outputs are IS galvanically isolated from the source
 All channels are independently IS limited

Understanding System Planning

Part of system planning is determining what modules are needed for the
application, how many power supplies are needed, how to best partition the
system, and where to locate the system cabinets.
A key task in the development cycle is determining the number of power
supply outputs (thus power supplies) you will need. In the following example,
you will need eleven power outputs if you are using the fiber hub, which
requires 8.5 W.

Each power supply has four independent IS-power outputs capable of 8.5 W
each. In the above example, we required 11 IS-power outputs so three power
supplies were sufficient.

Modules

Requires

Modules

Requires

Fiber hub

8.5 W

Two thermocouple inputs

1.6 W each

Two ControlNet

adapters

8.5 W each

Two digital outputs

7.5 W each

Two analog inputs

7.5 W each

Three NAMUR digital inputs

2.8 W each

Two analog outputs

6.3 W each

Two counter inputs

4.25 W each