0 installation, 1 wiring, 2 initial installation – Rockwell Automation 61C615 RTD Termination Panel User Manual

Page 11

Advertising
background image

3Ć1

3.0 INSTALLATION

This section describes how to install and remove the termination

panel and its cable assembly.

3.1

Wiring

The installation of wiring should conform to all applicable codes.
To reduce the possibility of electrical noise interfering with the proper

operation of the control system, exercise care when installing the

wiring from the system to the externaldevices. For detailed

recommendations refer to IEEE 518.

3.2

Initial Installation

WARNING

THERE IS NO ISOLATION BETWEEN THE INDIVIDUAL CHANNELS ON THE

TERMINATION PANEL. DO NOT CONNECT DIFFERENT CHANNELS ON THE

SAME TERMINATION PANEL TO COMMON POINTS OF DIFFERENT

POTENTIALS. (FOR EXAMPLE, THIS PANEL SHOULD NOT BE CONNECTED TO

RTD DEVICES USED TO MONITOR MOTOR TEMPERATURES BECAUSE THE RTD

DEVICES WILL FLUCTUATE IN COMMON MODE VOLTAGE LEVEL BETWEEN THE

DIFFERENT MOTORS.) FAILURE TO OBSERVE THIS PRECAUTION MAY

DESTROY THE TERMINATION PANEL DUE TO EXCESSIVE CURRENTS FLOWING

IN THE COMMON WIRING.

Use the following procedure to install the module:
Step 1.

Turn off power to the system. All power to the rack as well

as all power to the wiring leading to the termination panel

should be off.

Step 2.

Mount the termination panel. It should be mounted to

permit easy access to the screw terminals on the terminal

board. Make certain that the terminalboard is close

enough to the rack so that the cable will reach between

the terminalboard and the module. The panelshould be

located so that the flat cables can be routed to the front of

the module without coming in contact with high voltage

wires.

Step 3.

Mount the external power supply. It must be located within

a 6Ćft cable run of the termination panel. It should be

located so that the power cable can be routed to the

termination panelwithout coming in contact with high

voltage wires.

Step 4.

Connect the power cable on the termination panel to the

power supply.

Step 5.

Fasten field wires to the terminal strip. Make certain that all

field wires are securely fastened. The shield should be

terminated at the panel. Do not connect the shield at both

ends of the cable. Typical field signal connections are

shown in figure 3.1.

Advertising