background image

2Ć1

2.0 MECHANICAL/ELECTRICAL

DESCRIPTION

The following is a description of the termination connectors and

electrical characteristics of the fieldconnections.

2.1

Mechanical Description

The 61C615 is a 19" rackĆmountable termination panel that includes

two 6Ćfoot, 50Ćwire twistedpair flat cables anda 6Ćfoot power cable. A

separately mounted+15 volt power supply is provided by the user.

Refer to figure 2.1. Panel dimensions are listed in Appendix A.
When the panel is viewedfrom the front, the flat cable on the right

side of the termination panel (TB2) is for analog inputs 8Ć15. It

connects to the bottom connector on the 61C613. The flat cable on

the left side of the termination panel (TB1) is for analog inputs 0Ć7. It

connects to the middle connector on the 61C613. The top connector

on the 61C613 module is not used.
The termination panel includes 64 clampĆtype screw terminals for

terminating fieldsignals. A clear plastic shieldis providedas a cover

for the terminal strips.

Figure 2.1Ć 61C615 Termination Panel

2.2

Electrical Description

The RTD termination panel is usedto linearize andpower 100 ohm

platinum Resistance Temperature Detectors usedwith the 61C613

analog input module. The resistance change of the RTD with

temperature is sensedby using the RTD as the external 4th arm of a

bridge. The termination panel contains the internal portions of the

bridge as well as the bridge excitation supply. See figure 2.2.

Advertising