AĆ2
Appendix A
(Continued)
Power Requirements
D +15 Volts: 100 mA
D -15 Volts: 160 mA
D Voltage tolerance: +1%
D Voltage temp Coef.: 0.02%/deg.C
D Line regulation: 0.1%
D Load regulation: 0.1%
D Ripple: <2 mVolts RMS
D Protection: Each line fused at 1A and reverse voltage protected.
D Fuse type: Littelfuse 276001
D Connector: 3 wire cable, 6 ft. long with spad lugs
+15 Volts Ć yellow
-15 Volts Ć violet
ground Ć gray
WARNING
UNUSED INPUTS SHOULD BE CLOSED. OPEN INPUTS CAN CAUSE Ć15V
CURRENT TO INCREASE BY15MA PER CHANNEL AND +15V CURRENT TO
INCREASE BY10MA PER CHANNEL. JUMPER SENSE" TO HIGH R" (GROUND)
AT ALL UNUSED INPUTS. FAILURE TO OBSERVE THIS PRECAUTION COULD
RESULT IN BODILYINJURYOR DAMAGE TO EQUIPMENT.