24 FLEX Ex Bus Isolator and Flexbus Connector

Publication

1797-5.13 - June 2010

I/O module capacitance value is cumulative. Ci (total) = Ci (I/O module

1) + Ci (I/O module 2) + ...Ci (I/O module 8). Ci (total) must be less than
65 F. The limitation of eight I/O modules per isolator is a functional
limitation. Refer to table 2 of the appropriate I/O Modules sections in this
document (1797-6.5.6).

Application

The isolator type 1797-BIC/* module functions as a galvanic isolation barrier
for signals between a nonintrinsic backplane bus and an intrinsic safe
backplane bus. The isolator must be installed in a safe or Zone 2 area.

Cover Plug for IS Backplane Bus

The 16-pole male connector for the FLEX Ex IS backplane bus is provided
with a cover plug. The cover plug can only be removed when a 1797-TB3
terminal base, a 1794-CE1 cable or a 1794-CE3 cable is connected. The
connection must not be connected to any signals that exceed the instrinsically
safe values of the IS backplane.

Power Supply

The isolator is powered via a removable terminal connector with a dc-voltage
between 18V and 32V. Due to a failure in the power supply a maximum
voltage U

m

of 253V ac is permitted.

Isolator

Restriction

1797-BIC and -CEC

Max of 8 I/O modules

IMPORTANT

For detailed certification information, refer to the FLEX Ex
System Certification Reference Manual, publication
1797-6.5.6.